Raisio Data Center

Raisio Data Center

FACILITY SPECIFICATIONS
  • Stone built space underground
  • Height of the latticed ceiling of the facility is 3.0 metres of available space
  • Colocation site and corridor access routes are a minimum of 2.30 metres
  • Overhead cabling (electricity and IT network)
  • Surface materials are fireproof
  • EMP- protected
  • Ceiling structures are leak protected against water
  • System availability 99.999% per annum
  • Tiering level Tier 2

AIR CONDITIONING AND COOLING
  • Data Center is overpressured 10-20% in relation to the environment
  • Temperature 23 ± 2°C. Our goal is to raise room temperature higher in order to save energy. Alarm limits: temperature min. 18°C, max. 27°C
  • Cooling package units N+1
  • Closed cooling system.
SECURITY AND ACCESS
  • Data Center is under 24/7 security and video surveillance
  • Electronic access control, limited access; authorized personnel only
  • Centralized alarm system. All alarms are received by Elisa
  • Route leading to the underground parking and loading space with access control

FIRE CONTROL
  • Fully monitored automated detection and alarming
  • Underground facility is equipped with sprinklers and water damage prevention system in the colocation spaces
  • Alarms are transferred directly to local fire and rescue department and Elisa
  • Underground facility is equipped with a forced smoke abatement

FLEXIBLE DATA CENTER SERVICES
  • We offer customized Data Center services from shared rooms to private suites to meet your business needs
  • Data Center Connectivity Service providing global access
 
POWER SUPPLY
  • Data Center is connected to 20 kV national power grid
  • Multiple pieces electricity transformers
  • Distribution network, backed up by diesel generators, delivers power to UPS, cooling, extinction and security systems N+1
  • Use of reserve power up to 7 days