Säterinportti Data Center Espoo
FACILITY SPECIFICATIONS
Concrete built space
Height of the latticed ceiling of the facility is 3.0 metres of available space
Colocation site and corridor access routes are a minimum of 2.30 metres
Raised floor for electricity, IT cabling and cooling
Surface materials are fireproof
System availability 99.999% per annum
Tiering level Tier 1
AIR CONDITIONING AND COOLING
Data Center is overpressured 10-20% in relation to the environment
Temperature 23 ± 2°C. Our goal is to raise room temperature higher in order to save energy. Alarm limits: temperature min. 18°C, max. 27°C
Cooling package units N+1
Closed cooling system. In the summer time cooling is implemented with water cooling technology, in the winter time with fresh air cooling system
SECURITY AND ACCESS
Data Center is under 24/7 security and video surveillance
Electronic access control, limited access; authorized personnel only
Centralized alarm system. All alarms are received by Elisa
FIRE CONTROL
Fully monitored automated detection and alarming
Facility is equipped with inergen system in the colocation spaces
Alarms are transferred directly to local fire and rescue department and Elisa
Facility is equipped with a forced smoke abatement
POWER SUPPLY
Data Center is connected to 20 kV national power grid
Multiple pieces electricity transformers
Distribution network, backed up by diesel generators, delivers power to UPS, cooling, extinction and security systems N
Use of reserve power up to 7 days
FLEXIBLE DATA CENTER SERVICES
We offer customized Data Center services from shared rooms to private suites to meet your business needs
Data Center Connectivity Service providing global access